Roof Vent Calculator

Calculate how much attic ventilation area you need, split between intake and exhaust vents.

Total floor area of the attic space being ventilated.

Use 300 if the attic has a vapor barrier and balanced intake/exhaust; use 150 without a vapor barrier.

Check the vent product spec — a typical static roof vent provides about 50 sq in of net free area.

Attic ventilation is sized off the attic's floor area using a simple ratio: 1 square foot of net free ventilating area (NFVA) for every 150 square feet of attic, or 1:300 if the attic has a proper vapor barrier and the ventilation is split evenly between intake and exhaust. That total NFVA is then divided roughly in half — half at the soffits as intake, half at the ridge or roof as exhaust — because air has to come in low and exit high for the system to actually work, not just add vents wherever there's room.

Frequently Asked Questions

What is the 1:150 vs 1:300 rule for attic ventilation?

It is the ratio of attic floor area to required net free ventilating area. Use 1:150 (1 sq ft of NFVA per 150 sq ft of attic) as a conservative default, or 1:300 if the attic has a vapor barrier and the intake/exhaust is properly balanced.

Should intake and exhaust vents be equal?

Yes, most building codes and manufacturers require a roughly 50/50 split between intake (usually soffit vents) and exhaust (usually ridge or static roof vents) so air flows continuously from low to high points in the attic.